Automatic transfer, grid-parallel and generator-parallel systems solve different electrical tasks. Each requires an agreed source arrangement, protection basis, control sequence, operating authority and functional test plan.

Inputs to prepare

  • Utility, generator, bus and essential-load single-line diagram
  • Voltage, current, fault level, neutral, earthing and protection requirements
  • Permitted interruption, start and transfer time, load steps, redundancy and reserve
  • Utility import or export limits, metering, synchronization and interconnection rules
  • Remote commands, communications, operating authority and maintenance isolation needs

Decisions to confirm

  • ATS source positions, neutral switching, interlocking, bypass and manual operation
  • Grid-parallel synchronization, power control, unloading, trip and reconnection
  • Generator start priority, synchronization, load sharing, low-load strategy and stop order
  • Load shedding, degraded modes, black-start and failure-recovery behavior
  • Switchgear form, access, arc-safety, cable entry and future expansion

Review before release

  • Review protection settings and selectivity against the final equipment
  • Simulate loss and restoration of every source
  • Test interlocks, permissives, manual modes and emergency stops
  • Record synchronized closing, load transfer, shedding, unloading and trip behavior
  • Retain approved logic, settings, test results and as-built single-line